PVC and CPVC Common Venting
With Non-Return Flue Check Valve
PVC and CPVC Common Venting
With Non-Return Flue Check Valve
WARNING
If the information in these instructions is not followed exactly, a fire or explosion
may result causing property damage, personal injury or death.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a licensed professional.
PLEASE NOTE THIS SYSTEM MAY NOT BE AVAILABLE IN SA AT THE MOMENT
Welcome
This manual provides installation instructions for
PVC/CPVC common venting with a non-return flue
check valve and is a supplement to the Installation and
Operations Manual supplied with the Rinnai Tankless
Water Heater. Common venting with PVC and CPVC
must satisfy all the requirements of the Installation and
Operations Manual, as well as the requirements in this
manual.
For detailed information on the Rinnai Tankless Water
Heater, including installation instructions, refer to the
Tankless Water Heater Installation and Operation
Manual or view an online version at rinnai.us.
To The Installer
This manual is intended for the installer and is
designed for licensed installers who should have skills
such as:
Gas sizing
Connecting gas lines, water lines, valves, and
electricity
Knowledge of applicable national, state, and
local codes
Installing venting through a wall or roof
Training in installation of tankless water heaters.
Training on Rinnai Tankless Water Heaters is
accessible at www.trainingevents.rinnai.us
A licensed installer must test the PVC/CPVC common
vent system for leaks before use.
The installation must conform to the Rinnai Tankless
Water Heater Installation and Operation Manual that
is shipped with the unit, local codes, or in the
absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54.
Read all instructions contained in this manual before
installing the Non-Return Flue Check Valve; the valve
must be installed according to the exact instructions
in this manual.
Proper installation is the responsibility of the
installer.
When installation is complete, give all manuals
related to the common venting installation (including
this manual and the Rinnai Water Heater Installation
and Operation Manual) directly to the consumer. The
manuals should be stored in a readily accessible
location for future reference.
To The Consumer
Keep this manual for future reference.
Be sure your PVC/CPVC common vent system,
including the Non-Return Flue Check Valve, is
installed by a licensed installer.
Contents
Welcome Page
If You Need Service 2
To The Installer 2
To The Consumer 2
1. Safety 3
1.1 Safety Symbols 3
2. About PVC/CPVC Common Venting 4
2.1 Venting Guidelines 4
2.2 Derate and Total BTU 5
2.3 High Altitude Installations 5
2.4 Items Included 6
2.5 Items Needed For Installation 6
2.6 Items Not Required 6
2.7 About the Non-Return Flue Check Valve 6
3. Install the Venting 7
Venting Installation Sequence 7
For The Installer 7
3.1 Choose the Installation Location 8
3.2 Install Check Valve to Water Heater 9
3.3 Assemble the Header 12
3.4 Connect the Venting 14
3.5 Terminate the Venting 15
3.6 Set DIP Switches 18
3.7 Connect Cables 19
3.8 Post Installation Checklist 19
READ ALL INSTRUCTIONS BEFORE INSTALLATION
IMPORTANT
The Non-Return Flue Check Valve (Rinnai Part # 790111) is referred to as
“check valve” throughout the remainder of this manual.
WARNING
If the information in these instructions is not
followed exactly, a fire or explosion may result
causing property damage, personal injury, or death.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
The warning signs in this manual are here to
prevent injury to you and others. Please follow
them explicitly.
WARNING
Installations must comply with local requirements
and with the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 for U.S. installations.
Installations are certified for Direct Vent applications
only. DO NOT install in Room Air applications.
Use only 3” and 4” Schedule 40 Solid Core PVC/
CPVC. DO NOT use any other type of venting
material, including cellular core PVC (ASTM F891),
cellular core CPVC, Radel® (polyphenolsulfone), ABS,
or galvanized material.
Use only the materials listed in this section for vent,
air intake pipe, and fittings. Failure to comply with
this warning could result in property damage,
personal injury, or death.
DO NOT operate the unit until venting is completely
installed and all solvents and glues have bonded.
Failure to comply with this warning could result in
property damage, personal injury, or death.
DO NOT slope the combustion air pipe toward unit.
Failure to comply with this warning could result in
property damage, personal injury, or death.
DO NOT apply PVC/CPVC glues, solvents, or cleaners
to the tankless water heater’s intake or exhaust
gasket connections. Failure to correctly assemble
the components according to these instructions may
result in property damage, personal injury, or death.
PVC/CPVC common venting cannot be used if the
following conditions exist:
The tankless water heater is installed in a
recirculation system and the thermostat setting
is greater than 150 F (65.5 C).
The tankless water heater is used in a
combination domestic water and space heating
application that requires a thermostat setting
greater than 150 F (65.5 C).
PVC/CPVC common venting is not approved for use
in Canada.
2. About PVC/CPVC Common
Venting
PVC/CPVC common venting allows multiple Rinnai
Tankless Water Heaters to share the same vent system,
which means fewer wall or roof cuts, less labor, and
longer vent lengths than with single-unit tankless water
heater venting.
PVC/CPVC common venting is CSA-certified (ANSI
Z21.10.3, Gas Water Heaters Standards) for use with the
following Rinnai Condensing Tankless Water Heaters:
■ RUR98i (REU-KBP3237FFUD-US)
■ RU98i (REU-KB3237FFUD-US)
■ RUC98i (REU-KBD3237FFUD-US)
■ C199i (REU-KBD3237FFUDC-US)
■ DEMAND DUO (CHS199100)
Additional Features:
For use with 3”, 4” and 6” Schedule 40 Solid Core
PVC/CPVC
In-line or back-to-back configurations
Horizontal or vertical terminations
Certified for Direct Vent applications only; do not
install in Room Air applications.

2.1 Venting Guidelines
![]()
Do not install in separate distribution systems. All water
heaters common vented must be in the same hot and
cold plumbing manifolds and must not exceed 3 units.
Do not connect the venting system with an existing vent
or chimney.
Do not combine vent components from different
manufacturers.
Do not common vent with the vent pipe of any other
type of water heater or appliance.
Do not install the water heaters in an area of negative
pressure.
Do not install the water heaters, venting, and vent
termination(s) in any areas where the air may contain
corrosive compounds.
Do not use adhesives to connect PVC/CPVC to the check
valve.
Do not use cellular core PVC (ASTM F891), cellular core
CPVC, Radel® (polyphenolsulfone), ABS, or galvanized
material for the exhaust vent.
Do not cover non-metallic vent pipe and fittings with
thermal insulation.
Do not reduce vent diameter.
Do not install in Room Air applications.

The tankless water heater is a direct vent water heater.
Use only the vent components specified in this manual.
The tankless water heater must be set to long vent
length by adjusting DIP switch #1 in the first group of
switches (DIP SW 1) to the OFF position.
The vent system must vent directly to the outside of the
building and use outside air for combustion.
Avoid dips or sags in horizontal vent runs by installing
supports per this manual’s instructions.
Support horizontal vent runs a minimum of every four
feet and all vertical vent runs a minimum of every six
feet.
Venting should be as direct as possible with a minimum
number of pipe fittings.
Vent connections must be attached together so that
they form an air tight seal.
Install a check valve onto each tankless water heater.
Use only the check valve specified in this manual. Use
only the lubrication supplied with purchase to attach
PVC/CPVC to the check valve (water is an optional
lubricant).
The combustion air intake must be connected to the
water heater and secured with (1) self-tapping screw
(supplied with purchase).
Set the temperature setting on all tankless water
heaters being common vented to the same
temperature.
Information
When operating two or more tankless water
heaters in a PVC common venting system, it is
recommended to use Rinnai’s EZConnect cable
(for 2 tankless water heaters) or MSB-M Kit (for 2
or 3 tankless water heaters).
Rinnai recommends replacing the check valve
when replacing the water heater.
Maintenance
Check and clean the check valve every 12 months,
or after 4,000 operation hours. The check valve is
to remain accessible by only using the supplied
lubricant (or optional water) on the 3” PVC/CPVC
inserted into the check valve.
Rinse the valves with lukewarm water using the
condensate outlet to flush.
Do not use aggressive or abrasive cleaning agents
as they can affect the functionality of the valves.
2.3 High Altitude Installations
High altitude installations are certified up to
10,200 Ft.
Approved gas type: Natural and Liquid Propane.
Ensure the tankless water heaters are properly
installed and set up for the altitude at which they
will be operating.
High Altitude Derate
PVC and CPVC common vent systems at altitudes over
2,000 Ft. will automatically derate according to the
tables below.

2.2 Derate and Total BTU
Tankless water heaters using common venting with PVC/
CPVC will automatically derate according to the table
below. Use the table below for calculating your total BTU
for multiple tankless water heaters using common
venting with PVC/CPVC.
* The MSB-M Kit (Multi-System Control Board) and EZ